TL-W5MC2 OMRON Proximity Switch NEW
Fiche technique | TL-W5MC2 Proximity Switch NEW |
OMRON Proximity Switch TL-W5MC2
Product Description:
Only 6 mm thick yet provides a sensing distance of 3 mm (TL-W3MC1).
Aluminum die-cast models also available.
Specifications:
Model | TL-W1R5MC1 | TL-W3MC[] | TL-W5MC[] | TL-W5E1 | TL-W20ME1 | |
TL-W5E2 | TL-W20ME2 | |||||
TL-W5F1 |
| |||||
TL-W5F2 |
| |||||
Sensing distance | 1.5 mm ±10% | 3 mm ±10% | 5 mm ±10% | 20 mm ±10% | ||
Set distance | 0 to 1.2 mm | 0 to 2.4 mm | 0 to 4 mm | 0 to 16 mm | ||
Differential travel | 10% max. of sensing distance | 1% to 15% of sensing | ||||
distance | ||||||
Detectable object | Ferrous metal | |||||
(The sensing distance decreases with non-ferrous metal. Refer to Engineering Data on Data Sheet.) | ||||||
Standard sensing object | Iron, | Iron, | Iron, | Iron, | ||
8 × 8 × 1 mm | 12 × 12 × 1 mm | 18 × 18 × 1 mm | 50 × 50 × 1 mm | |||
Response frequency | 1 kHz min. | 600 Hz min. | 500 Hz min. | 300 Hz min. | 40 Hz min. | |
Power supply voltage | 12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max. | 12 to 24 VDC (10 to | 12 to 24 VDC | |||
(operating voltage | 30 VDC), ripple (p-p): | (10 to 30 VDC), | ||||
range) | 20% max. | ripple (p-p): 10% max. | ||||
Current consumption | 15 mA max. at 24 VDC (no-load) | 10 mA max. | 15 mA max. at 24 | 8 mA at 12 VDC, | ||
VDC (no-load) | 15 mA at 24 VDC | |||||
Control | Load | NPN open collector | NPN open collector | 200 mA | 100 mA max. | |
output | current | 100 mA max. at 30 VDC max. | 50 mA max. at 12 VDC | at 12 VDC | ||
|
|
| (30 VDC max.) | 200 mA max. | ||
|
|
| 100 mA max. at 24 VDC | at 24 VDC | ||
|
|
| (30 VDC max.) |
| ||
| Residual | 1 V max. (under load current of 100 | 1 V max. (under load | 2 V max. (under load | 1 V max. (under load | |
| voltage | mA with cable length of 2 m) | current of 50 mA with | current of 200 mA with | current of 200 mA with | |
|
|
| cable length of 2 m) | cable length of 2 m) | cable length of 2 m) | |
Indicators | Detection indicator (red) | |||||
Operation mode | NO | C1 Models: NO | E1/F1 Models: NO | |||
(with sensing object | C2/B2 Models: NC | E2/F2 Models: NC | ||||
approaching) | Refer to the timing charts under I/O Circuit Diagrams on Data Sheet for details. | |||||
Protection circuits | Reverse polarity protection, Surge suppressor | |||||
Ambient temperature | Operating/Storage: -25 to 70°C (with no icing or condensation) * | |||||
range | ||||||
Ambient humidity range | Operating/Storage: 35% to 95% (with no condensation) | |||||
Temperature influence | ±10% max. of sensing distance at 23°C in the temperature range of -25 to 70°C | |||||
Voltage influence | ±2.5% max. of sensing distance at | ±2.5% max. of sensing | ±2.5% max. of sensing distance at rated voltage | |||
rated voltage in the rated voltage | distance at rated voltage | in the rated voltage ±10% range | ||||
±10% range | in the rated voltage |
| ||||
| ±20% range |
| ||||
Insulation resistance | 50 MΩ min. (at 500 VDC) between current-carrying parts and case | |||||
Dielectric strength | 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case | |||||
Vibration resistance | Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions | |||||
Shock resistance | Destruction: 500 m/s2 3 times each in X, Y, and Z directions | Destruction: 500 m/s2 | ||||
10 times each in X, Y, | ||||||
and Z directions | ||||||
Degree of protection | IEC 60529 IP67, in-house standards: oil-resistant * | |||||
Connection method | Pre-wired Models (Standard cable length: 2 m) | |||||
Weight (packed state) | Approx. 30 g | Approx. 45 g | Approx. 70 g | Approx. 180 g | ||
Materials | Case | Heat-resistant ABS | Aluminum die-cast | Heat-resistant ABS | ||
Sensing | Heat-resistant ABS | |||||
surface | ||||||
Accessories | Mounting Bracket, | Instruction manual | ||||
Instruction manual |
For environments that require oil resistance, the upper limit of the ambient operating temperature range is 40°C.
Le produit ne peut pas être utilisé normalement à cause de problèmes de qualité dans la période de garantie
Les marchandises sont endommagées pendant le transport
Si un retour est requis, les frais de retour seront payés par nous
L’acheteur enverra un courriel au personnel du service clientèle pour décrire les problèmes et fournir les documents d’attestation(les photos, les captures d’écran ou les vidéos claires)
Nous examinerons les problèmes dans un délai d’un à trois journées de travail. Pour ceux qui répondent aux exigences, nous fournirons un remplacement gratuit ou un remboursement dans un délai d’un à deux journées de travail
Si les marchandises doivent être retournées, nous payons les frais d'expédition de retour
TL-W5MC2 Proximity Switch NEW
Gross Weight | 0.05 |
---|